LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 76

background image

Page 72

LAARS Heating Systems

Name

PW?

Function

How to get there

Demand switch (CH)

-

Set to “STAT terminal.”

Info/ Advanced Setup/ CH

Configuration

DHW pump control

Y

The boiler pump can be turned on manually, or it

can be set to operate automatically.

Info/ Test/ Manual Pump Operation
Info/ Advanced Setup/ System

Config./ Pump Config.

DHW pump cycle count

Y

A new value can be written here if the pump or

controller is replaced.

Info/ Advanced Setup/ System

Config./ Statistics Config.

DHW pump overrun time Y

This indicates how long the DHW pump will remain

on after demand from any source ends.

Info/ Advanced Setup/ System

Config./ Pump Config.

DHW setpoint

-

This setpoint is used to control the Domestic Hot

Water function.

quick Start
Info/ Advanced Setup/ DHW

Configuration

Digital I/O

-

This shows the status of selected switches and

valves that are either On or Off.

Info/ Diagnostics

Display setup

-

Use this to change the lines that appear at the top

of the Home display, and to set the brightness of the

display.

Info/ Display Setup

General configuration

-

Used by the Laars factory.

Info/ Advanced Setup/ System

Config./ System Config.

I gain (CH)

Y

This gain is applied to the Integral term of the PID

equation for the CH loop.

Info/ Advanced Setup/ CH

Configuration

I gain (DHW)

Y

This gain is applied to the Integral term of the PID

equation for the DHW loop.

Info/ Advanced Setup/ DHW

Configuration

I gain (LL)

Y

When using the Lead/ Lag system to control

multiple boilers –
This gain is applied to the Integral term of the PID

equation for the hydronic heating loop.

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Master Config.

Installer password

Y

This can only be changed by a user with the OEM-

level password.

Info/ Advanced Setup/ System

Config./ System ID and Access

LCD contrast

-

Use this to change the brightness of the display.

Info/ Display Setup

Lockout history

-

This displays the 15 most recent lockouts.

Info/ Diagnostics/ History

Low water temp. (CH)

-

Used with Outdoor Reset –
Above the point where Outdoor Reset stops

adjusting for a higher outdoor temperature (the Max.

Outdoor Temperature value), this parameter is used

as the setpoint.

quick Start
Info/ Advanced Setup/ CH

Configuration/ Outdoor Reset Config.

Low water temp. (LL)

-

When using the Lead/ Lag system to control

multiple boilers, with Outdoor Reset enabled –
Above the point where Outdoor Reset stops

adjusting for a higher outdoor temperature (the Max.

Outdoor Temperature value), this parameter is used

as the setpoint.

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Outdoor Reset

Manual burner operation Y

During testing, use this to turn the burner on and off. Info/ Test

Master enable (LL)

-

When using the Lead/ Lag system to control

multiple boilers –
One of the controllers must be set up as the Lead/

Lag Master to supervise the Lead/lag system. The

master function must be disabled on all of the other

controllers. See the section on “About Lead/Lag.”

Info/ Advanced Setup/ Lead Lag

Configuration/ LL Master Config.