beautypg.com

LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 88

background image

Page 84

LAARS Heating Systems

187

Invalid DHW (Domestic Hot

Water) high limit enable setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

188

Invalid DHW (Domestic Hot

Water) high limit response setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

189

Invalid flame sensor type setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

192

Invalid igniter on during setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

193

Invalid ignite failure delay setting L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

194

Invalid ignite failure response

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.\

195

Invalid ignite failure retries setting L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

196

Invalid ignition source setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

197

Invalid interlock open response

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

198

Invalid interlock start check

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

199

Invalid LCI (Limit Control Input)

enable setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

200

Invalid lightoff rate setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

201

Invalid lightoff rate proving

setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

202

Invalid MFEP (Main Flame

Establishing Period) time setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

203

Invalid MFEP (Main Flame

Establishing Period) flame failure

response setting

L

1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

Code Description

L or H Procedure

This manual is related to the following products: