LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual
Page 81

Page 77
N
eo
T
herm
Boilers and Water heaters
12
Internal fault:
Safety relay drive cap short
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
13
Internal fault:
PII (Pre-Ignition Interlock)
shorted to ILK (Interlock)
H or L Internal fault
1. Reset module
2. If fault repeats, replace module.
15
Internal fault:
Safety relay test failed due to
feedback ON
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
16
Internal fault:
Safety relay test failed due to
safety relay OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
17
Internal fault:
Safety relay test failed due to
safety relay not OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
18
Internal fault:
Safety relay test failed due to
feedback not ON
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
19
Internal fault:
Safety RAM write
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
20
Internal fault:
Internal fault: Flame ripple and
overflow
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
21
Internal fault:
Flame number of sample
mismatch
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
22
Internal fault:
Flame bias out of range
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
23
Internal fault:
Bias changed since heating cycle
starts
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
24
Internal fault:
Spark voltage stuck low or high
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
25
Internal fault:
Spark voltage changed too much
during flame sensing time
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
26
Internal fault:
Static flame ripple
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
Code Description
L or H Procedure