Appendix B -
ERROR MESSAGES
This table includes a listing of the faults that might be generated by the controller, and displayed on the Operator
Interface. Some of these can be corrected by an installer changing a parameter, while other conditions are more
complicated, and will require a service technician.
The first column lists the code number that will appear at the beginning of the Lockout or Hold message. The second
column lists a short description of the condition. The third column shows whether the condition will cause a Hold, or
Lockout, or both. The fourth column lists some suggestions for corrective action.
Code Description
L or H Procedure
1
Unconfigured safety data
L
1. New device, complete device configuration and safety verification.
2. If fault repeats, replace module.
2.
Waiting for safety
data verification
L
1. Device in Configuration mode and safety parameters need
verification and a device needs reset to complete verification.
2. Configuration ended without verification, re enter configuration,
verify safety.
parameters and reset device to complete verification.
3. If fault repeats, replace module.
3
Internal fault:
Hardware fault
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
4
Internal fault:
Safety Relay key feedback error
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
5
Internal fault:
Unstable power (DC) output
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
6
Internal fault:
Invalid processor clock
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
7
Internal fault:
Safety relay drive error
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
8
Internal fault:
Zero crossing not detected
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
9
Internal fault:
Flame bias out of range
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
10
Internal fault:
Invalid burner control state
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
11
Internal fault:
Invalid burner control state flag
L
Internal fault
1. Reset module
2. If fault repeats, replace module.