Page 80

LAARS Heating Systems

94

Header sensor fault

H

1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, replace the module.

95

Stack sensor fault

H

1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, replace the module.

96

Outdoor sensor fault

H

1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, replace the module.

97

Internal Fault: A2D mismatch.

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

98

Internal Fault: Exceeded VSNSR

voltage tolerance

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

99

Internal Fault: Exceeded 28V

voltage tolerance

L

Internal Fault.
1. Reset module.
2. If fault repeats, replace module.

100

Pressure Sensor Fault

H

1. Verify the pressure sensor is a 4-20 mA source.
2. Check wiring and correct any possible errors.
3. Test the pressure sensor for correct operation.
4. Replace the pressure sensor.
5. If previous steps are correct and fault persists, replace the module.

105

Flame detected out of sequence

H or L 1. Check that flame is not present in the combustion chamber. Correct

any errors.
2. Make sure that the flame detector is wired to the correct terminal.
3. Make sure the F & G wires are protected from stray noise pickup.
4. Reset and sequence the module. If code reappears, replace the

flame detector.
5. Reset and sequence the module. If code reappears, replace the

module.

106

Flame lost in MFEP

L

1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame detector

siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the

module.

107

Flame lost early in run

L

1. Check main valve wiring and operation - correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame detector

siting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace the

module.

Code Description

L or H Procedure