beautypg.com

8c.8 cascading lead/lag operation – LAARS NeoTherm NTV (Sizes 150–850 MBTU/h) - Install and Operating Manual User Manual

Page 46

background image

Page 42

LAARS Heating Systems

Boiler Pump Interrupt Function -
The Boiler pump interrupt feature is used in some applications

when the boiler is being used for both hydronic and domestic

hot water heating. The interrupt jumper is used to turn off

the boiler pump during a domestic hot water demand. For

this to work properly the system must be plumbed and

pumped to allow the DHW pump to supply the flow and head

requirements for both the boiler and indirect water heater. It is

not necessary to use the interrupt jumper in all applications.
To turn off the Boiler pump in this situation, the “boiler pump

interrupt” jumper should be installed between R1 and R2 on

TB5.
If your system includes several boilers, is controlled using the

Lead/Lag system, and the indirect DHW tank is connected

to the boiler acting as the Lead/Lag master, install the boiler

interrupt jumper on the Lead/Lag master only.

WARNING

Failure to plumb, pump and install the appliance

correctly when using this feature may lead to reduced

or no water flow through the heat exchanger, causing

premature failure of the heat exchanger, personal

injury or death. Please consult the factory with any

questions regarding the use of this feature.

Setup for DHW Control Functions -
1. Set up the correct priority for the DHW function in relation

to Central Heat or Lead/ Lag demands. If a call for heat

and a DHW demand arrive at the same time, which will

have the higher priority?
If your system has just one boiler –
How to get there: From the “Home” screen, press “I”

to go to “Info/ Install.” Choose “Advanced Setup,” then

go to “DHW Configuration.” Select “DHW Priority vs

Central Heat.”
If your system has more than one boiler, and is controlled

using the Lead/ Lag function –
How to get there: On the unit used as the Lead/Lag

Master, from the “Home” screen, press “I” to go to “Info/

Install.” Choose “Advanced Setup,” then go to “DHW

Configuration.” Select DHW Priority vs Lead/Lag.”

2. Set the setpoint for the DHW function.

If your system has just one boiler –
How to get there: From the “Home” screen, press “I” to

go to “Info/ Install.” Choose “Advanced Setup,” then go

to “DHW Configuration.” Select “DHW Setpoint.”
If your system has more than one boiler, and is controlled

using the Lead/ Lag function –
How to get there: On the unit used as the Lead/Lag

Master, from the “Home” screen, press “I” to go to “Info/

Install.” Choose “Advanced Setup,” then go to “DHW

Configuration.” Select “DHW Setpoint.”

3. Set the DHW priority time. If the DHW function has the

priority, the priority will continue during the priority time.
If your system has just one boiler –
How to get there: From the “Home” screen, press “I” to

go to “Info/ Install.” Choose “Advanced Setup,” then go

to “DHW Configuration.” Select “DHW Priority Time.”
If your system has more than one boiler, and is controlled

using the Lead/ Lag function –
How to get there: On the unit used as the Lead/Lag

Master, from the “Home” screen, press “I” to go to “Info/

Install.” Choose “Advanced Setup,” then go to “DHW

Configuration.” Select “DHW Priority Time.”

8C.8 Cascading Lead/Lag Operation

About Lead/Lag Operation -
If an installation includes two or more boilers, they may be

set up for “Lead/Lag” operation. One boiler will be set up as

the “Master”, and the others will operate as “Slaves.” Figure

38 shows an installation with four boilers. (A Lead/Lag

system can include up to eight boilers.) The boiler controllers

are connected in a “daisy chain” using a Modbus connection.

See Fig. 40.
A single System sensor is used to monitor the demand

for heat. The input from this sensor is used by the Master

controller to control the modulation rates of all of the

operating boilers.

Lead/Lag Modulation Cycle -
Note - We will explain the modulation cycle here, in case

you need to understand how the Lead/Lag system actually

operates. If you are installing the unit(s) and want to skip this

section, just remember that, as the heating demand increases,

the Lead/Lag system puts more boilers on-line. As the

heating demand is reduced, the Lead/Lag system shuts off

some of the boilers.
The signal from the System sensor is sent to the unit

operating as the Lead/Lag Master. A Run sequence is

initiated when the system temperature falls to the Lead/Lag

Central Heat setpoint. (Actually this is the LL CH setpoint

less the On Hysteresis value. The default setting for On

Hysteresis is 5°F, but this is adjustable.)

NOTE: If your NeoTherms are Lead / Lag configured,

you will find it very useful to customize your Home

Display to show LL Operating Temp and LL Setpoint

Temp.

Please refer to Section 7.5 to learn how to customize

your Home Display. Various parameters can be displayed

on the Home Display to suit your needs.

This manual is related to the following products: