159
Main valve Off
L
1. Check the main valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the
module.
160
Ignition On
L
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the
module.
161
Ignition Off
L
1. Check the ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persists, replace the
module.
164
Block intake On
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage across the switch.
Supply voltage should be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
165
Block intake Off
L
1. Check wiring and correct any errors.
2. Inspect the Block Intake Switch to make sure it is working correctly.
3. Reset and sequence the module.
4. During Standby and Purge, measure the voltage across the switch.
Supply voltage should be present. If not, the Block Intake Switch is
defective and needs replacing.
5. If the fault persists, replace the relay module.
172
Main relay feedback incorrect
L
Internal fault.
1. Reset module.
2. If fault repeats, replace module.
174
Safety relay feedback incorrect
L
Internal fault.
1. Reset module.
2. If fault repeats, replace module.
175
Safety relay open
L
Internal fault.
1. Reset module.
2. If fault repeats, replace module.
176
Main relay On at safe start check L
Internal fault.
1. Reset Module.
2. If fault repeats, replace module.
178
Safety relay On at safe start
check
L
Internal fault.
1. Reset module.
2. If fault repeats, replace module.
184
Invalid Blower/ HSI output setting L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
185
Invalid Delta T limit enable
setting
L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
186
Invalid Delta T limit response
setting
L
1. Recheck selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.