Configuration screens (cont) – Carrier OMNIZONE 50XJ064-104 User Manual
Page 51

51
Configuration Screens (cont)
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
DESCRIPTION
VALUE*
UNITS
NAME
OMNIZONE::DSALM08: Compressor 1 Alarm
Monitored Input Point
C1_ALM
Name
Comparison Point
SENSDI00
Name
Alarm Inhibit Point
SENSDI00
Name
Discrete Check
Alarm Logic
Normal
AlmLogic
Enable Delay Time
10
sec
DlyTim
Persistence Time
10
sec
Persist
Alarm Processor
Alarm Processing
Enable
AlmProc
Re-Alarm Interval
0
min
ReAlmTim
Alarm=1 or Alert=0
1
Type
Alarm Level
2
AlmLevel
Alarm Source
5
AlmSrc
Alarm Routing
11010000
AlmRtg
Alarm Description Index
0
AlmDesc
Alarm Message - Part 1
Compressor 1 fau
Message
Alarm Message - Part 2
lt
Message
Alarm Message - Part 3
Message
Alarm Message - Part 4
Message
Power on Delay
0
sec
PowerUp
OMNIZONE::DSALM09: Compressor 2 Alarm
Monitored Input Point
C2_ALM
Name
Comparison Point
SENSDI00
Name
Alarm Inhibit Point
SENSDI00
Name
Discrete Check
Alarm Logic
Normal
AlmLogic
Enable Delay Time
10
sec
DlyTim
Persistence Time
10
sec
Persist
Alarm Processor
Alarm Processing
Enable
AlmProc
Re-Alarm Interval
0
min
ReAlmTim
Alarm=1 or Alert=0
1
Type
Alarm Level
2
AlmLevel
Alarm Source
5
AlmSrc
Alarm Routing
11010000
AlmRtg
Alarm Description Index
0
AlmDesc
Alarm Message - Part 1
Compressor 2 Fau
Message
Alarm Message - Part 2
lt
Message
Alarm Message - Part 3
Message
Alarm Message - Part 4
Message
Power on Delay
0
sec
PowerUp
OMNIZONE::DSALM10: Compressor 3 Alarm
Monitored Input Point
C3_ALM
Name
Comparison Point
SENSDI00
Name
Alarm Inhibit Point
SENSDI00
Name
Discrete Check
Alarm Logic
Normal
AlmLogic
Enable Delay Time
10
sec
DlyTim
Persistence Time
10
sec
Persist
Alarm Processor
Alarm Processing
Enable
AlmProc
Re-Alarm Interval
0
min
ReAlmTim
Alarm=1 or Alert=0
1
Type
Alarm Level
2
AlmLevel
Alarm Source
5
AlmSrc
Alarm Routing
11010000
AlmRtg
Alarm Description Index
0
AlmDesc
Alarm Message - Part 1
Compressor 3 Fau
Message
Alarm Message - Part 2
lt
Message
Alarm Message - Part 3
Message
Alarm Message - Part 4
Message
Power on Delay
0
sec
PowerUp