beautypg.com

Automatic run test, 10 table 6 — quick access chart – Carrier OMNIZONE 50XJ064-104 User Manual

Page 10

background image

10

Table 6 — Quick Access Chart

LEGEND

NOTES:

1. To change from Edit mode to Status mode, press

or press

again.

2. Not all available selections will have items to select in sublevels.

Automatic Run Test —

The 50BV,XJ unit controls are

programmed with an automatic run test that checks connection
and operation of major components. To perform the run test:

Verify that the control display (LID device/System Monitor)

interface cable is connected to internal jack on main controller;
that the fire alarm/shutdown switch input (FSD) has a factory
jumper or field input; that Bypass (if installed) is set in the
DRIVE position; and that the Local/Off/Remote switch is set to
the REMOTE position.
NOTE: When the Local/Off/Remote switch is in the
REMOTE position, the controller time schedule is pre-set
(from the factory) as unoccupied. This means that the unit
will not turn on until the run test is enabled. However, if the
controller schedule has already been modified in the field,
and the current time of day is occupied, then the supply fan
will start. The run test will shut the fan down when it

begins. The run test will complete and then the supply will
automatically restart.
NOTE: If the Local/Off/Remote switch is in the OFF posi-
tion, it is normal for the red alarm light on the display panel
to be lit, indicating that the unit is disabled.
NOTE: If the red light stays on when the switch is moved to
REMOTE, or if any other problems occur during the run
test, refer to the Troubleshooting section of this manual.

To perform the Run Test:

1. Turn unit power on.

The LID display will show the controller identifica-
tion, time and date (Fig. 5):
OMNIZONE VPAC

hh:mm mm-dd-yy

LID

NUM.

KEY

LID FUNCTION KEYS

Algorithms

(ALGO)

Status
(STAT)

History

(HIST)

Service

(SRVC)

Alarm

(ALRM)

Setup

(SET)

Schedules

(SCHD)

1

AO—Adaptive Control

Hardware Points

Alarm History

Function Definition

Limit

Set Clock

Occupancy

2

AO—Cooling CV

Software Points

Analog Point Trace

Channel Definition

Setpoint

Real Time Clock

Setpoint

3

AO—Cooling VAV

Temperature Input

Discrete Point Trace

System Definition

Discrete

Controller Password

Holiday

4

AO—Fan Tracking

Milliamp Input

Consumable Channel

Setpoint Definition

First out

N/A

S/W Setpoint

5

AO—Heating CV

Custom Milliamp Input

Internal Consumable

Database Control

Runtime

N/A

Network Time

6

AO—Heating VAV

Voltage Input

Runtime Channel

Comfort Controller

# of starts

N/A

N/A

7

AO—Humidity Control

Custom Voltage Input

N/A

CCN Control

N/A

N/A

N/A

8

AO—Mixed Air CV w/IAQ

Sensed Discrete Input

N/A

LID Preferences

N/A

N/A

N/A

9

AO—Mixed Air VAV w/IAQ

Latched Discrete Input

N/A

N/A

N/A

N/A

N/A

10

AO—Permissive Interlock

Pulsed Discrete Input

N/A

N/A

N/A

N/A

N/A

11

AO—Reset

Milliamp Output

N/A

N/A

N/A

N/A

N/A

12

AO—Shared Transducer

Custom Milliamp Output

N/A

N/A

N/A

N/A

N/A

13

AO—Static Pressure

Voltage Output

N/A

N/A

N/A

N/A

N/A

14

DO—Analog

Custom Voltage Output

N/A

N/A

N/A

N/A

N/A

15

DO—DX-Staging VAV

Discrete Output

N/A

N/A

N/A

N/A

N/A

16

DO—Electric Heat CV

Stepper Motor Output

N/A

N/A

N/A

N/A

N/A

17

DO—Electric Heat VAV

Discrete Software Point

N/A

N/A

N/A

N/A

N/A

18

DO—Enthalpy Comparison

Analog Software Point

N/A

N/A

N/A

N/A

N/A

19

DO—Interlock

Network Data Out

N/A

N/A

N/A

N/A

N/A

20

DO—Lighting Control

Network Data In

N/A

N/A

N/A

N/A

N/A

21

DO—Permissive Interlock

N/A

N/A

N/A

N/A

N/A

N/A

22

DO—Pump Control

N/A

N/A

N/A

N/A

N/A

N/A

23

DO—Prop Thermo

N/A

N/A

N/A

N/A

N/A

N/A

24

DO—Prop Thermo 2 Pipe

N/A

N/A

N/A

N/A

N/A

N/A

25

DO—Prop Thermo 4 Pipe

N/A

N/A

N/A

N/A

N/A

N/A

26

DO—Staged Thermostat

N/A

N/A

N/A

N/A

N/A

N/A

27

DO—Staging Control

N/A

N/A

N/A

N/A

N/A

N/A

28

DO—Time Clock

N/A

N/A

N/A

N/A

N/A

N/A

29

DO—Time Clock w/Check

N/A

N/A

N/A

N/A

N/A

N/A

30

AOSS Schedule

N/A

N/A

N/A

N/A

N/A

N/A

31

Network Broadcast

N/A

N/A

N/A

N/A

N/A

N/A

32

Linkage/AOSS Schedule

N/A

N/A

N/A

N/A

N/A

N/A

33

NTFC w/Enthalpy Check

N/A

N/A

N/A

N/A

N/A

N/A

34

Sensor Group

N/A

N/A

N/A

N/A

N/A

N/A

35

WSM Air Source

N/A

N/A

N/A

N/A

N/A

N/A

36

WSM Cool Source

N/A

N/A

N/A

N/A

N/A

N/A

37

Custom Program

N/A

N/A

N/A

N/A

N/A

N/A

AO

Analog Output

AOSS — Adaptive Optimal Start/Stop
CV

Constant Volume

DO

Digital Output

IAQ

Indoor Air Quality

N/A

Not Available

NTFC

Nighttime Free Cooling

VAV

Variable Air Volume

WSM

Water System Manager

CLEAR

EXPN/EDIT