2.5 ENABLING REMOTE SETPOINT CONFIGURATION ON THE
AERCO EUROTHERM TEMPERATURE CONTROLLER
The setpoint may be programmed to be remotely configured by executing the following steps.
See the previous instructions for changing communication addresses in the AERCO Eurotherm
Temperature Controller for more detailed directions for programming the controller.
1) Page to “ACCS”.
2) Scroll and enter code of 1.
3) Scroll and at the “GOTO” menu choose “Conf”.
4) At the “Conf” screen enter the code of 2
5) Press the Scroll button once and then the Page button until you find “SP”.
6) Scroll until you find “rmt” and set the parameter value to “SP”.
7) Press the Page and Scroll button together at the same time to go to “exit”.
8) Press the Up arrow to select “yes” and then the instrument will reboot.
9) Once the instrument has returned to its normal state, press the Page button until you see
“SP”.
10) Scroll until you see “L-r” and using the Up arrow select “rmt”.
11) Once you have selected “rmt” press the Page and Scroll buttons at the same time to return
to the normal temp display.
You should now be able to control the set point remotely.