beautypg.com

Troubleshooting, Link/activity indicator (link/act), System failure indicator (sf) – KEYENCE DL-PN1 User Manual

Page 24

background image

22

- PROFINET Communication Unit DL-PN1 User's Manual (GT) -

Troubleshooting

The indicator LEDs on the DL-PN1 can be used to determine the causes of errors.

Link/activity indicator (LINK/ACT)

This indicator indicates whether the DL-PN1 is communicating correctly.

System Failure indicator (SF)

This indicator indicates whether the DL-PN1 is operating normally.

Link/activity indicator (Green)

System Failure indicator (Orange, Red)

Bus Failure indicator (Red)

Sensor communication indicator (Green, Red)

LED Status

Condition

Corrective Action

Green

Solid

The DL-PN1 is normally linked.

-

Flashing

The DL-PN1 is normally linked and is
now exchanging data.

-

Not lit

Power is not supplied to the DL-PN1.
The DL-PN1 is not linked.

• Check if the power supply is correctly connected.
• Check if the DL-PN1 is correctly connected to the

sensor amplifier.

• Check if the IP address is correct.
• Check if the power supply of the connected device

or Ethernet switch is correctly connected.

• Check if the cable is correctly connected.

LED Status

Condition

Corrective Action

Solid red

There may be a system error on the
DL-PN1 or a connected sensor.

• Check the D-bus LED status.
• Check if the number of connected sensor

amplifiers exceeds the maximum number of
connectable units.

• Check if the IP address is correct.
• Check if the slot number is correct.
• Check if the DL-PN1 is correctly connected to the

sensor amplifier.

• Check if there is an electrical noise source near the

DL-PN1.

Flashing orange

Flash LED was requested on the I/O
controller.
Flashes approximately 4 times per
second.

-

Not lit

The DL-PN1 is normally operating.

-