KEYENCE DL-DN1 User Manual
Page 67

5-2 Troubleshooting
5-5
5
A
p
pe
nd
ix
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (FD-MH) -
Sensor communication indicator
This lamp indicates whether the DL-DN1 is communicating properly with sensor
amplifiers.
The cause of the error can be identified by reading the error code through I/O
communication or explicit messaging.
"Error information list" (page 3-8)
LED status
Condition
Corrective action
Not lit
Power is not supplied to the 
DL-DN1.
Check that the DL-DN1 is cor-
rectly connected with the sensor
amplifiers.
Green
Solid
Communicating correctly.
-
Flashing
In process of power-on 
reset.
After the power-on reset time 
has elapsed, the DL-DN1 auto-
matically switches to the normal 
state.
Red
Flashing at 
fixed inter-
vals
Temporarily unable to com-
municate with sensor ampli-
fiers.
Check for any noise source 
around the DL-DN1. (The error 
is automatically corrected after 
the cause is removed.)
Repeating 
of 4 con-
secutive 
flashes
Model error (0003h)
Connect a sensor amplifier of a 
compatible model.
Mixed connection error 
(0004h)
Remove the incompatible sen-
sor amplifier.
Number-of-units error 
(0006h)
Observe the number of connect-
able sensor amplifiers.
Solid
Initialization error
(0001h/0002h/0005h)
Check the number of connected 
sensor amplifiers and the con-
nection to the sensor amplifiers, 
and then cycle power. If the 
error can not be restored, con-
tact your nearest sales office.
Sensor-to-sensor communi-
cation error
(0007h)
Check the connections of the 
sensor amplifiers, and then 
cycle power.