3-3 Explicit Messaging
3-25
3
Co
mm
u
ni
c
a
ting
w
ith t
he FD
-M
H
s
er
ie
s
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (FD-MH) -
N: ID number of sensor amplifier
Setting/status command parameters
For the communication methods using setting/status parameters, see
Writing Settings or Status of a Sensor Amplifier" (page 3-20).
Attribute R: Read; W: Write; R/W: Read/Write
N: ID number of sensor amplifier. For example, if the ID number is 13, then N x 10 + 3
-> 133 (DEC).
The data types are DINT unless explicitly specified.
InstID
(DEC)
AttrID
(HEX)
Name
Description
Attrib ute
N
64
Group-0 entr y count
The def ault v alue is 5.
R
65
System reser ve d
66
Integrated fl
ow quantity reset
request
Resets integrated fl
ow quantity .
C
67
Reset request dur ing hold
(instantaneous fl
ow rate)
Resets instantaneous fl
ow hold va lu e.
C
68
Reset request dur ing hold
(temperature displa y)
Resets temperature hold v alue .
C
69
Initial reset request (ALL)
Resets all settings of the sensor ampli fi
er to
the f actor y def ault settings .
C
InstID
(DEC)
AttrID
(HEX)
Name
Description Attribute
Sensor
head
Default
value
Parameter range
Nx10+1
64
Group-1 entry count
R
-
22
65
Sensor amplifier
error state
*1
R
-
-
Bit 0: Head error (ErH)
Bit 1: Head connection error (ErH)
Bit 2: Overcurrent error (ErC)
Bit 3: EEPROM error (ErE)
Bit 4: Always 0
Bit 5: Always 0
Bit 6: Backfl ow error (rEv)
Bit 7: Always 0
Bit 8: Temperature lower limit error
Bit 9: Temperature upper limit error
Bit 10: Temperature sensor connection error
(Err tEMP)
Bits 11 - 15: Always 0
66 to
67
System reserved
68
Control output, integra-
tion pulse output, error
alarm output states
*2
R
-
-
Bit 0: Output 1
Bit 1: Output 2
Bit 2: Output 3
Bits 3 - 15: Always 0