Installation and Operation Handbook

Tuning

2408 and 2404 Controller

4-9

5. Press

or

to turn ‘

PCAL’ to ‘on’.

6. Press

and the upper readout indicates ‘

Pot’.

7. Press

or

to get to ‘

Pot-3A.Hi’. (Assuming that the Potentiometer Input

Module is in module position 3.)

8. Press

to go to ‘

GO-no’.

9. Press

or

to see ‘

GO-YES’, which starts the calibration procedure.

10. Calibration is complete when the display returns to ‘

GO-no’.

11. Press

and

together to return directly to the Operator level.

12. The controller should still be in Manual mode.
13. Drive the valve to its fully closed position using

.

14. Press

until you get to ‘

ip-List’.

15. Press

to get to ‘

PCAL-OFF’.

16. Press

or

to turn ‘

PCAL’ to ‘on’.

17. Press

and the upper readout indicates ‘

Pot’.

18. Press

or

to get to ‘

Pot-3A.Lo’

19. Press

to go to ‘

GO-no’.

20. Press

or

to see ‘

GO-YES’, which starts the calibration procedure.

21. Calibration is complete when the display returns to ‘

GO-no’.

22. Press

and

together to return directly to the Operator level.

23. Press the AUTO/MAN button to place the controller in AUTO and the calibration of the

position feedback potentiometer is now complete.