2408 and 2404 Controller
2-13
Name
Description
ProG
Program edit list
− Present only in setpoint programming controller.
For a fuller explanation of these parameters refer to Chapter 5
PrG.n
Select program number (Only on
4, or 20, program versions)
Hb
Holdback type for the program as a whole (if configured)(
OFF, Lo, Hi, or bAnd)
Hb V
Holdback value (in display units)
rmP.U
Ramp units (
SEc, min, or Hour) [for both rmP.r and rmP.t type segments]
dwL.U
Dwell units (
SEc, min, or Hour)
CYC.n
Number of program cycles (
1 to 999, or ‘cont’)
SEG.n
Segment number
tYPE
Segment type:
(
End) (rmP.r=ramp rate) (rmP.t=ramp time) (dwel) (StEP) (cALL)
The following parameters depend on the
tYPE selected, as shown below.
End rmP.r rmP.t dwEl StEP cALL
Hb
Holdback type:
OFF, Lo, Hi, or bAnd
tGt
Target setpoint for a ‘
rmP’ or ‘StEP’ segment
rAtE
Ramp rate for a ‘
rmP.r’ segment
dur
‘
dwEl’ time / Time to target for a ‘rmP.t’ segment
PrG.n
cALLed ProGram number
cYc.n
No. of cycles of cALLed program
outn
Event output:
OFF/on
(not 8-segment programmer)
SYnc
Segment synchronisation:
no/YES
(not 8-seg progr)
End.t
End of prog
− dwEl, RSEt, S OP