beautypg.com

Amps, Amps ---- disp – Thermcraft XST-3-0-36-3V User Manual

Page 150

background image

Load Current Monitoring and Diagnostics Installation and Operation Handbook

D-4 2408 and 2404 Controller

OPERATION

To Read Load Current (modes 2 and 5 only)

Do This

This Is The Display You Should See

Additional Notes

From the ‘

InFo’ list

Press

until

AmPS is shown in

the upper display











It will revert to the
HOME display after
45 seconds or 10
seconds if an alarm
is present


To Display Load Current Continuously in the Lower Readout (modes 2 and 5
only)

Do This

This Is The Display You Should See

Additional Notes

From the ‘HOME’
display, Figure 1.4,

Press

until

diSP is shown in

the upper display

Press

or

until

AmPS is

displayed in the
lower display

Current will be
displayed in the
lower readout
continuously when
the controller reverts
to the HOME
display, see also
‘Display Modes’
below.

Display Modes

SSR RMS On State Current

This is the default state when high or low current alarms are configured. The load current
displayed is the steady state true rms current measured during the ON period.
The minimum on times are:-
Mode 2

0.1second

Mode 5

3 seconds

Meter Mode

Meter mode applies to mode 5 only. If low current alarms are not configured the current
displayed is a filtered instantaneous RMS value. This behaves like a damped analogue meter.
It may be used in applications where the current sensor is not linked to control, for example,
telemetry, indication.

AmPS

5

AmPS
----

diSP

AmPS

Current will be displayed in
the lower readout. See
also ‘Display Modes’
below.

This display will be shown if:
I. The controller is unable to resolve the reading
II. The controller is obtaining a reading
III. The measurement has timed out i.e. current has

not flowed for 15 seconds, in mode 2.

This manual is related to the following products: