Thermcraft XST-3-0-36-3V User Manual
Page 262

Load Current Monitoring and Diagnostics
Installation and Operation Handbook
8-8
2416 Controller
8.8
TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS
Alarm 1 will be configured as Load Current Low (
Lcr)
Alarm 2 will be configured as Load Current High (
Hcr)
Do This
This Is The Display You Should See
Additional Notes
Press
button
until the
AL Conf
is displayed
This opens the
configuration list
which contains the
Alarms
Press
to show
AL1 (alarm 1)
Press
or
to show
LCr
To select alarm 1
To make alarm 1 =
Low Current
Press
until
AL2 (alarm 2)
appears
Press
or
to show
HCr
After 0.5 sec the display
will blink to show the
alarm type has been
accepted
To select alarm 2.
To make alarm 2 =
High Current
Note:- The above alarms are known as SOFT ALARMS because they are indication
only.
AL
Conf
AL1
LCr
AL2
HCr