3-22

BROADway - Release 4.00

Configuration

Setting System Node Parameters

To view the power input redundancy status of the system, use the RTRV-EQPT TL1 command:

RTRV-EQPT::NSP-x.PWR-1:1234;

To enable or disable power input redundancy, use the ED-EQPT TL1 command:

ED-EQPT::NSP:1234::;

ENA, ENABLE, ENABLED, DIS, DISABLE, or DISABLED.

Examples:

Enable power supply input redundancy (assuming NSP-1 is the active NSP):

ED-EQPT::NSP:1234::ENA;

Disable power supply input redundancy (assuming NSP-1 is the active NSP):

ED-EQPT::NSP:1234::DIS;

If you have installed two separate power sources to the BROADway chassis (both FEED A and
FEED B on the back of the chassis), you should enable power input supply redundancy. (For
information about connecting these power feeds, see Cabling Power and Ground on page 2-6.) If you
do not have two separate power sources connected to the chassis, you should disable power supply
redundancy; otherwise, the NSP PWR alarm LED will lamp red (as described in the online help).