ULTRA-CUT 100 XT/200 XT/300 XT/400 XT

Manual 0-5264

SPECIFICATIONS

2-3

Ultra-Cut 100 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps) Wire (AWG)

Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

21

31

40-45

#12

4

Ultra-Cut 200 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps)

Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

42

62

100

#6

16

Ultra-Cut 300 XT™ Power Supply

Input

Power Input

Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps) Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

63

93

150

#4

25

IEC

400

50/60

72

106

150

#4

25

Ultra-Cut 400 XT™ Power Supply

Input

Power Input Current

Suggested Sizes (See Note)

Voltage

Freq.

3-Ph

3-Ph

Fuse (Amps)

Wire (AWG) Wire (mm

2

)

(Volts)

(Hz)

(kVA)

(Amps)

3-Ph

3-Ph

3-Ph

400

50/60

93

137

200

#1

50

NOTE

* Suggested wire size based on United States NFPA 70 National Electrical Code 2011 edition pub�

lished by the National Fire Prevention Association. Listings are from table 400.5(A)(2) for flexible cord

of certain types rated for 75 deg C in a�bient te�peratures up to �0 deg C� Using wires of lower te��

deg C in a�bient te�peratures up to �0 deg C� Using wires of lower te��

C in a�bient te�peratures up to �0 deg C� Using wires of lower te��

perature rating or different insulation type �ay require larger wire size� De rate for higher a�bient�

These are suggestions only� Always refer to your local and national codes that apply to your region for

final determination of correct wire type and size.