beautypg.com

Testing the control, Test, Range access level description item field – tekmar 369 Zone Control Installation User Manual

Page 27

background image

Copyright © D 369 -10/00

27 of 32

369 RTU Misc (Miscellaneous) Menu (1 of 1)

USER

°F, °C
Default =

°F

ADV, INST, USER, LTD

Default = INST

OFF, 30 sec, ON

Default = ON

The operating mode for the back lighting on the LCD
as well as the time of keypad inactivity until the control
automatically returns to the default display.

BACKLITE = OFF (returns after 10 seconds)
BACKLITE = 30 s (returns after 30 seconds)
BACKLITE = ON (returns after 90 seconds)

The units of measure that all of the temperatures are
to be displayed.

The access level that is to be used by the RTU.

DIP switch =

Unlock

Displays which

tn1 terminal on the 369 this RTU is

connected to.

RTU1. . . RTU6

LT

D

INST ADV

Range

Access
Level

Description

Item Field

R

TU 062

R

TU 063

not testing
testing
testing paused

Test

off
red
red

Testing the Control

The Zone Control 369 has a built in test routine which is used to test the
main control functions. The 369 continually monitors the sensors and
displays an error message whenever a fault is found. See the following
pages for a list of the 369’s error messages and possible causes. When
the

Test button is pressed, the test light is turned on. The individual out-

puts and relays are tested in the following sequence.

TEST SEQUENCE

Each step in the test sequence lasts 10 seconds.

During the test routine, the test sequence is paused by pressing the

Test button. While paused, the control displays the testing step

as well as the word PAUS. If the

Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits

the entire test routine. If the test sequence is paused, the

Test button can be pressed again to advance to the next step. This can

also be used to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the

Test button

until the appropriate device and segment in the display turn on.

Step 1

- The system pump

(Sys Pmp) relay is turned on for 10 seconds. After 10 seconds, the Sys Pmp relay is shut off.

Step 2

- If COOL MOD is set to ENBL or CTRL, the control turns on the

Cooling relay for 10 seconds. After 10 seconds, the Cooling

relay is shut off.

Step 3

- If zone 1 (tN1 1) is used for a one stage heating zone, the control turns on relay Zn 1 for 10 seconds. After 10 seconds,

the

Zn 1 relay is shut off. If an RTU is not connected to tN1 1, the control skips this step.

Step 4

- If zone 2 (

tN1 2 or Indr 2) is used for a one stage heating zone, the control turns on relay Zn 2 for 10 seconds. After 10

seconds, the

Zn 2 relay is shut off.

- If zone 2 (

tN1 2 or Indr 2) is used for a two stage heating zone, the control turns on relay Zn 1 for 10 seconds. After 10

seconds, the

Zn 1 relay is shut off. The Zn 2 relay is then turned on for 10 seconds. After 10 seconds, the Zn 2 relay is

shut off.

- If an RTU or indoor sensor is not connected to

tN1 2 or Indr 2, the control skips this step.

Step 5

- The control tests relay

Zn 3 using the procedure described in Step 3.

Step 6

- The control tests relay

Zn 4 using the procedure described in Step 4.

Step 7

- The control tests relay

Zn 5 using the procedure described in Step 3.

Step 8

- The control tests relay

Zn 6 using the procedure described in Step 4.

- 01/09

- 01/09