369 Monitor Menu (1 of 2)

The highest recorded outdoor air temperature since this item
was last cleared. This can be used to diagnose if the Outdoor
Sensor 070 has been located correctly. If this reading is too
high the 070 may be located in a location that receives direct
sun light or is influenced by an exhaust vent.

0 to 9999 hr

-67 to 149

°F

(-55 to 65

°C)

0 to 9999 hr

0 to 9999 hr

0 to 9999 hr

0 to 9999 hr

0 to 9999 hr

-67 to 149

°F

(-55 to 65

°C)

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

The lowest recorded outdoor air temperature since this item
was last cleared. This can be used to diagnose if the Outdoor
Sensor 070 has been located correctly. If this reading is too
high there may not be adequate insulation behind the 070, or
it may be too close to an exhaust vent.

The total number of system pump

(Sys Pmp) running hours

since this item was last cleared.

The total number of

Cooling relay running hours since this

item was last cleared.

The total number of

Zn 1 relay running hours since this item

was last cleared.

The total number of

Zn 2 relay running hours since this item

was last cleared.

The total number of

Zn 3 relay running hours since this item

was last cleared.

The total number of

Zn 4 relay running hours since this item

was last cleared.

Note: To clear the recorded information in the specific item field, press and hold

▲ and ▼.

35 to 100

°F

(2 to 38

°C)

Default = 70

°F (21°C)

35 to 100

°F

(2 to 38

°C)

Default = 65

°F (18°C)

NONE, STRT, STOP,
BOTH

Default = BOTH

Desired room air temperature during an
occupied period.

(Indoor sensor is present.)

Desired room air temperature during an
unoccupied period.

(Non-display RTU or indoor sensor is present.)
DIP switch =

Setback

Enables or disables the Optimum Start / Stop
feature for this zone.

(Non-display RTU or indoor sensor is present.)
DIP switch =

Setback

A1

C

Occ

369 Zone Adjust Menu (2 of 2)

C

Actual

Setting

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

UnOcc

- 01/09