369 RTU Monitor Menu (1 of 1)

The highest outdoor air temperature recorded since
this item was last cleared.

USER

-67 to 140

°F

(-55 to 60

°C)

The lowest outdoor air temperature recorded since
this item was last cleared.

-67 to 140

°F

(-55 to 60

°C)

The highest room air temperature recorded since this
item was last cleared.

20 to 120

°F

(-7 to 49

°C)

The lowest room air temperature recorded since this
item was last cleared.

20 to 120

°F

(-7 to 49

°C)

This is an adjustable item. If the air temperature
measured by the RTU exceeds this setting, the control
will display a warning message.

50 to 120

°F, OFF

(10 to 49

°C, OFF)

Default = OFF

This is an adjustable item. If the air temperature
measured by the RTU drops below this setting, the
control will display a warning message.

OFF, 20 to 80

°F

(OFF, -7 to 27

°C)

Default = OFF

Note: To clear the recorded information in the specific item field, press and hold

▲ and ▼.

LT

D

INST ADV

Range

Access
Level

Description

Item Field

R

TU 062

R

TU 063

369 RTU Time Menu (1 of 1)

:00 to :59

Default = :00

SATURDAY, . . . ,
FRIDAY

Default = SATURDAY

12: AM to 11: PM or
00: to 23:

Default = 12: AM

12 hr, 24 hr

Default = 12 hr

Real time clock minutes.

DIP switch =

Setback

Real time clock hours.

DIP switch =

Setback

Day of the week.

DIP switch =

Setback

Method of displaying time in the display.

DIP switch =

Setback

AM

Display time of day and the day of the week.

DIP switch =

Setback

R

TU 062

R

TU 063

AM

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

- 01/09

- 01/09