Menus, View menu, Control adjust menus – tekmar 369 Zone Control Installation User Manual

Page 18: Range access level description item field

background image

Copyright © D 369 -10/00

18 of 32

369 View Menu (1 of 1)

Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.

– – –, -67 to 149

°F

(-55 to 65

°C)

– – –, -58 to 167

°F

(-50 to 75

°C)

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

– – –, -58 to 167

°F

(-50 to 75

°C)

– – –, -58

° to 167°F

(-50 to 75

°C)

– – –, -58 to 167

°F

(-50 to 75

°C)

– – –, -58

° to 167°F

(-50 to 75

°C)

– – –, -58 to 167

°F

(-50 to 75

°C)

Current room air temperature of zone 1.

Current room air temperature of zone 2.

Current room air temperature of zone 3.

Current room air temperature of zone 4.

Current room air temperature of zone 5.

Current room air temperature of zone 6.

This is the signal that is being received from a zone control.

OFF, 30 to 110

°F

(OFF, -1 to 43

°C)

This is the signal that is being sent to a reset or additional
zone control.

OFF, 30 to 110

°F

(OFF, -1 to 43

°C)

A1

A1

A1

A1

A1

A1

A1

A1

A1

369 Control Adjust Menu (1 of 2)

Actual

Setting

NONE, ENBL, CTRL

Default = NONE

0:30 to 5:00 min

Default = 2:00 min

0:30 to 10:00 min

Default = 5:00 min

A U TO , 5 : 0 0 t o
30:00 min

Default = 15:00 min

The operating mode for the

Cooling relay.

If COOL MOD = CTRL, a display RTU must be
connected to tN 6

The minimum run time for the

Cooling relay.

COOL MOD

≠ NONE

The minimum off time for the

Cooling relay.

COOL MOD

≠ NONE

The cycle length used for cooling operation.

COOL MOD = CTRL

B1

B1

B1

B3

USER

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

- 01/09

- 01/09