Actual

Setting

PUMP, VLV, THRM

Default = VLV

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

ONE, TWO

Default = ONE

NONE, CG

Default = CG

NONE, CTRL

Default = NONE

The type of zoning device that is to be used.

(RTU or indoor sensor is present.)

Selects single stage or two stage operation.

(RTU or indoor sensor is present in even zone,
and RTU is not present in the preceding
odd zone.)

Selects if this zone is part of the cooling group.

(RTU or indoor sensor is present; Zone 1 to Zone 5.)
COOL MOD

≠ NONE

Selects if this zone is operated on the control
schedule.

(Non-display RTU or indoor sensor is present.)
DIP switch =

Setback

A1

A2

A3

B1

C

Note: The Zone Adjust menu is repeated for each zone that an RTU or indoor sensor is connected to. The Zone Adjust menu is indicated
by

Adjust in the left hand side of the display, and Zone followed by the zone number in the bottom of the display.

369 Zone Adjust Menu (1 of 2)

0:10 to 3:00 hr

Default = 0:30 hr

NONE, STRT

Default = NONE

0:30 to 4:00 min

Default = 3:00 min

0:10 to 2:00 min

Default = 0:30 min

OFF, 0:10 to 4:00 min

Default = 0:30 min

5:00 to 30:00 min

Default = 15:00 min

30 to 240 hr, OFF

Default = 70 hr

The time the heating zones assigned to the
cooling group must be off before cooling operation
is allowed.

COOL MOD

≠ NONE

Enables or disables the Optimum Start feature
for the cooling system.

COOL MOD = CTRL

The time required for a thermal zone valve to
open.

any ZNi OUTP = THRM (

i = 1, . . ., 6)

The time required for a thermal zone valve to
close.

any ZNi OUTP = THRM (

i = 1, . . ., 6)

The maximum length of time that a zone device
and the system pump continues to operate after
a heat demand is removed.

The cycle length used for heating operation.

The frequency with which the control exercises
the pumps and valves that are operated by
the control.

B1

B3

A1

A1

A1

A1

A1

369 Control Adjust Menu (2 of 2)

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

Actual

Setting