Item Field

Range

Access

Description

VIEW

2

0 to 100 %

or

1 to 4

ADV

BOILER 2 MODULATION / STG

SECTION D

Current percent modulation of the boiler 2 burner.
If the BTC I / Off DIP is set to BTC I, the BTC I
number of stages is displayed.
Note: This item is only available when boiler 2 is
set to Auto or CP1.

VIEW

3

0 to 100%

or

1 to 4

ADV

BOILER 3 MODULATION / STG

SECTION D

Current percent modulation of the boiler 3 burner. If
the BTC I / Off DIP is set to BTC I, the BTC I number
of stages is displayed.
Note: This item is only available when boiler 3 is set
to Auto or CP1.

VIEW

4

0 to 100%

or

1 to 4

ADV

BOILER 4 MODULATION / STG

SECTION D

Current percent modulation of the boiler 4 burner. If
the BTC I / Off DIP is set to BTC I, the BTC I number
of stages is displayed.
Note: This item is only available when boiler 4 is set
to Auto or CP1.

VIEW

1

hr

0 to 9999 hours

ADV

BOILER 1 RUNNING TIME

SECTION C

The total running time of boiler 1 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This
item is only available when boiler 1 is set to Auto.

VIEW

2

hr

0 to 9999 hours

ADV

BOILER 2 RUNNING TIME

SECTION C

The total running time of boiler 2 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This item
is only available when boiler 2 is set to Auto or CP1.

VIEW

3

hr

0 to 9999 hours

ADV

BOILER 3 RUNNING TIME

SECTION C

The total running time of boiler 3 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This item
is only available when boiler 3 is set to Auto or CP1.

VIEW

4

hr

0 to 9999 hours

ADV

BOILER 4 RUNNING TIME

SECTION C

The total running time of boiler 4 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item. Note: This item
is only available when boiler 4 is set to Auto or CP1.

VIEW

hr

Primary

1

0 to 9999 hours

ADV

PRIMARY PUMP 1 RUNNING TIME

SECTION L

The total running time of pump 1 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item.

VIEW

hr

Primary

2

0 to 9999 hours

ADV

PUMP 2 RUNNING TIME

SECTION L

The total running time of pump 2 since this item was
last cleared. To clear this item, press the up and down
buttons together while viewing this item.
Note: This item is only available when the Pump

Sequencer / Off DIP Switch is set to Pump
Sequencer.

After the last item, the control returns to the first item in the menu.

View Menu (2 of 2)