beautypg.com

Error messages (2 of 3) – tekmar 275 Boiler Control User Manual

Page 46

background image

©

2012 275_D

-

11/12

46

of

48

Error Message

Description

VIEW

SCHEDULE MASTER ERROR
More than one tekmarNet

®

device has been assigned the same master number.

VIEW

BOILER SUPPLY SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the boiler supply sensor. When there is a call
for heat, the control no longer controls the boiler(s). Instead, the control provides a boiler
enable to the boiler’s aquastat or boiler control until the sensor is repaired. The control will not
operate the boiler contact if the Boil Minimum setting is less than 100°F (38.0°C). Locate and
repair the problem as described in the data brochure D 070. The error message self clears
once the error condition is corrected.

VIEW

BOILER SUPPLY SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the boiler supply sensor. The control no longer
controls the boiler. Instead, the control provides a boiler enable to the boiler’s aquastat or boiler
control until the sensor is repaired. The control will not operate the boiler contact if the Boil
Minimum setting is less than 100°F (38.0°C). Locate and repair the problem as described in the
data brochure D 070. The error message self clears once the error condition is corrected.
Note: If you deliberately remove the boiler supply sensor, power down for 10 seconds then
restart the control.

VIEW

OUTDOOR SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the outdoor sensor. As a result, the control
assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair
the problem as described in the data brochure D 070. The error message self clears once
the error condition is corrected.

VIEW

OUTDOOR SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the outdoor sensor. As a result, the control
assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair
the problem as described in the data brochure D 070. The error message self clears once
the error condition is corrected.

VIEW

DEVICE SCHEDULE ERROR
The selected system schedule is no longer available. Either the system schedule master is
no longer connected to the network or the system schedule number has been changed on
the schedule master. The error message self clears once the error condition is corrected.

VIEW

DEVICE ERROR AT THERMOSTAT
There is an error on a thermostat or setpoint control that is connected to the 275. Find the
thermostat with this address to locate the source of the error. Once the error on the thermostat
or setpoint control is corrected, this error message will self clear.

VIEW

DHW SHORT CIRCUIT
Due to a short circuit, the control failed to read the DHW sensor. As a result, the control no
longer heats the DHW tank. Locate and repair the problem as described in the data brochure D
070. DHW tank heating will resume once the sensor problem is corrected. The error message
self clears once the error condition is corrected.

VIEW

DHW OPEN CIRCUIT
Due to an open circuit, the control failed to read the DHW sensor. As a result, the control no
longer heats the DHW tank. Locate and repair the problem as described in the data brochure D
070. DHW tank heating will resume once the sensor problem is corrected. The error message
self clears once the error condition is corrected.

Error Messages (2 of 3)