TABLE 3
VALVE

ASSEMBLY

VALVE

46 ACTUATOR

46 SPRING

4C ACTUATOR

4C SPRING

SPRING

STEM

VALVE

TYPE

ACTION

SIZE

PART #

PART#

PART #

PART#

QUANTITY

PART #

TRAVEL (in)

WM

N/A

1/2

672-022D

672-615

672-648D

672-646

6

672 636

1/8

N/A

1/2

672-022D

672-642

672-648D

672-646

6

672 636

1/8

N/A

3/4

672-022D

672-615

672-648D

672-646

6

672 636

3/16

N/A

3/4

672-022D

672-642

672-648D

672-646

6

672 636

3/16

N/A

1

672-022D

672-615

672-648D

672-646

6

672 636

1/4

N/A

1-1/4

672-022D

672-615

672-648D

672-646

4

672 636

5/16

N/A

1-1/2

672-022D

672-615

672-648D

672-646

4

672 636

5/16

N/A

2

672-022D

672-615

672-647D

672-646

4

672 636

5/16

MI N/A

2-1/2

672-671D

672-642

672-465D

672-646

6

672636B

5/8

N/A

3

672-671D

672-642

672-465D

672-646

6

672636B

3/4

N/A

4

672-671D

672-642

672-465D

672-646

6

672636B

1

*4X Actuators add 6 Springs #672-645.

MODIFICATION DATA TABLES

These tables provide actuator design information with regard to the
specific valve type and size. Use this information to determine
which springs to use, the number of springs required, and spring kit
part numbers.
These are the correct preload adjustments when mounting an
actuator on a valve or changing stems:
5 psi for NO assemblies
7-10 psi for NC assemblies
Use these pressure and the "Valve Travel" data to properly adjust the
stem length of your actuator/valve assembly.
Example:

Change a

Single Seat Stainless Trim reduced port 1/2A size valve, with a
normally open actuator assembly (593 VE A50 NO)

to a

Single Seat Stainless Trim 1/2" size valve with a Normally Closed
assembly (593 SS 050 NC).

1. Look up the references to the type of valve you want. In this

case, refer to the SS Valve Type, Table 4.

2. You need a new stem, part #672636A. You also need four

#672-615 springs.

3. Now install the new parts. Refer to the section on Changing

Actuator Action from DA to RA.

4. Also consult the section Changing Springs on a Reverse Acting

Actuator. See Figure 3A & B for Typical 4 Spring Installation
for symmetrical spring orientation.

TABLE 2

VALVE

ASSEMBLY

VALVE

46 ACTUATOR

46 SPRING

4C ACTUATOR

4C SPRING

SPRING

STEM

VALVE

TYPE

ACTION

SIZE

PART #

PART#

PART #

PART#

QUANTITY

PART #

TRAVEL (in)

SI

NO

2-1/2

672-672D

672- 642

672-466D

672-646

6

672-636B

5/8

NO

3

672-672D

672 -642

672-466D

672-646

6

672-636B

3/4

NO

4

672-672D

672 -642

672-466D

672-646

4

672-636B

1

NC

2-1/2

672-024R

672 -642

672-465R

672-646

6

672-636C

5/8

NC

3

672-024R

672 -642

672-465R

672-646

6

673-636C

3/4

NC

4

672-024R

672 -642

672-465R

672-646

6

673-636D

1

*4X Actuators add 6 Springs #672-645.

TABLE 1

VALVE

ASSEMBLY

VALVE

46 ACTUATOR

46 SPRING

4C ACTUATOR

4C SPRING

SPRING

STEM

VALVE

TYPE

ACTION

SIZE

PART #

PART#

PART #

PART#

QUANTITY

PART #

TRAVEL (in)

VE

NO

1/2A

672-022D

672-642

672-648D

672-646

6

672-636

1/4

NO

1/2B

672-022D

672-642

672-648D

672-646

6

672-636

1/4

NO

1/2C

672-022D

672-642

672-648D

672-646

6

672-636

1/4

NO

1/2D

672-022D

672-642

672-648D

672-646

6

672-636

1/4

NC

1/2A

672-024R

672-642

672-648R

672-646

6

672-636A

1/4

NC

1/2B

672-024R

672-642

672-648R

672-646

6

672-636A

1/4

NC

1/2C

672-024R

672-642

672-648R

672-646

6

672-636A

1/4

NC

1/2D

672-024R

672-642

672-648R

672-646

6

672-636A

1/4