INSTALLATION INSTRUCTIONS

VALVE SEAT AND REPAIR KIT

Accritem (Model 2 and 3)

A Watts Industries Co.

© Reprinted March 2002 Powers, a Watts Industries Co.

3400 Oakton Street, Skokie, IL 60076 Phone: 800.669.5430 • 847.673.6700 • Fax: 847.673.9044

www.powerscontrols.com

5435 North Service Road, Burlington, Ontario, L7L 5H7 Canada • Phone: 888.208.8927 • Fax: 888.882.1979

A Watts Industries Co.

1.

Turn adjusting knob clockwise to remove tension.

2.

Loosen set screw and remove knob.

3.

Remove six (6) cover screws and the cover.

4.

Remove spring retaining screw, and lever spring.

5.

Loosen two (2) pivot screws, and remove lever assembly.

a. Remove existing valve and valve spring form lever. On older models, the retaining washer was soldered to the valve. Later

construction has a “C” washer with jaws crimped over the valve stem.

b. Assemble new spring, valve and retaining washer onto lever as shown on Figure 1. Crimp jaws of retaining washer to

dimension shown on Figure 2.

6.

Replace old valve seat with new seat. Use 7/16” hex socket wrench.

7.

Reassemble parts in reverse order; take care that pivot screws are
snug without binding.

INSTALLATION INSTRUCTIONS

Form 129-051

Form 129-051 0218

EDP# 6512207

Printed in U.S.A.