SERIES 440 FOTOPANEL

Installation Instructions

IS-P-129_025

Need for Periodic Inspection/Maintenance: This product

must be tested periodically in compliance with local codes,

but at least once per year or more as service conditions

warrant. All products must be retested once maintenance

has been performed. Corrosive water conditions, inlet tem-

peratures over 200°F (93°C), and/or unauthorized adjustments

or repair could render the product ineffective for the service

intended. Regular checking and cleaning of the product’s

internal components helps assure maximum life and proper

product function.

WARNING

!

Installation

n

1. Flush all piping thoroughly before installing.
2. Remove knobs A, B, and C.
3. Remove the four-bracket screws (D) and panel screws (E)

then remove stainless steel box assembly.

Do not remove front panel from box.

There are six (6) bracket screws on the pressure

equalizing models.

4. For wall mounting, use rough-in drawing to locate mounting

holes on wall. Mount bracket to wall. Do not remove mixer

assembly from bracket.

5. Make final connections to hot and cold supplies and outlet

from vacuum breaker. Facing front of mixer, connect hot

water to left side (marked HOT) and cold water to right side

(marked COLD). Inlet connections must be piped correctly for

proper operation of Fotopanel.

Do not exert excessive torque on the outlet pipe when connecting

it to the vacuum breaker which is supported by a plastic manifold.
6. Replace stainless steel box assembly and attach knobs

A, B, and C and the front panel screws E.

WARNING

!

2-3/4"

3-5/8"

4-19/32"

4-19/32"

VERTICAL CENTER

LINE OF CABINET

MUST BE LEVEL

HOLE SIZE

(TO SUIT METHOD

OF FASTENING)

TOP EDGE OF CABINET

ROUGHING- IN DIMENSIONS

Thermometer Calibration

n

1. If thermometer should need calibration, remove front knobs

A, B, and C and the front panel screws E.

2. Calibration screw is located on back of thermometer case.

440-3000

CAPACITY

“A” “B” “C” “D” “E”

14 gpm

5-3/4

1-3/4

2-11/16 2-7/16

6-3/4

440-1000

CAPACITY

“A” “B” “C” “D” “E”

6 gpm

5-7/8

1-1/2

2-7/16

2-3/8

4-3/4

!