Troubleshooting
Restoring Factory Default Settings
Restoring the factory default settings resets the settings for:
Parameter
Default Setting
IP Address
192.168.0.1
Root Login
root
Root Password
sxi
HTTP Port
80
Modbus Server Port
502
Telnet Port
23
EtherNet/IP Protocol
Disabled
To restore these settings, leave the device powered up and running and
follow these steps:
1. Open the DX80 GatewayPro or DX83 Ethernet Bridge housing
to access the board
2. Install the initialization (init) jumper on the pins shown
3. Wait 30 seconds
4. Remove the jumper
5. Cycle power to the device
Using the configuration Web page, verify the parameters have returned to
the factory defaults listed in the table.
Serial Communication (RS-232 or
RS-485)
The GatewayPro and Ethernet Bridge devices use jumpers to select
between RS-485 and RS-232 communications. Because all DX80
devices are RS-485 based (at this time), verify the jumpers are set
correctly. Install the four jumpers across the two top rows of pins for
RS-485 and across the bottom two rows of pins for RS-232.
Initialization pins
Communications pins