Digital sensors, sinking (npn) outputs, Sensor connections – Banner SureCross DX80 Wireless Networks User Manual
Page 56

56
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
SureCross Wireless Network
Product Manual
Sensor Connections
DOx
PWR or SPx
SureCross Device
Wiring diagram for a sinking (NPN) two-wire
output.
Powered by DX80
Powered Externally
Two-Wire
Three-Wire
Digital Sensors, Sinking (NPN) Outputs
Neither the inputs nor the outputs on the DX80 devices are isolated. Under certain operating conditions, externally powered sensors may need
to have ground in common with the DX80 device to which they are connected. The power sources do not have to be the same.
GND
DOx
PWR
SureCross Device
Wiring diagram for a sinking (NPN) three-wire
output.
DOx
external
power
SureCross Device
Wiring diagram for a sinking (NPN) two-wire
output. Under certain conditions, the dc
commons between the sensor and the DX80
might need to be connected.
dc common
DOx
external
power
SureCross Device
Wiring diagram for a sinking (NPN) three-
wire output. Under certain conditions, the dc
commons between the sensor and the DX80
might need to be connected.