Analog inputs, Sensor connections, Powered by dx80 switch powered two-wire three-wire – Banner SureCross DX80 Wireless Networks User Manual
Page 57: Powered externally

57
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
SureCross Wireless Network
Product Manual
Sensor Connections
AIx
PWR
SureCross Device
Analog Inputs
For analog sensors, the ground/dc common of the sensor should be connected to the ground of the DX80 device. For best results, Banner
recommends that the power source for the sensor and DX80 device is the same.
SureCross Device
AIx or Ax+
SPx
SureCross Device
dc common
external
power
AIx or Ax+
GND
Three-wire analog sensor using a FlexPower
Node but the sensor is powered externally
(not from the DX80 device).
Two-wire analog sensor using a FlexPower™
Node and powered using the Node’s switch
power.
Two-wire analog sensor powered from a 10
to 30V dc power DX80 device using the PWR
terminal.
Powered by DX80
Switch Powered
Two-Wire
Three-Wire
AIx
GND
PWR
SureCross Device
Powered Externally
GND
SureCross Device
A1+
SP1
Three-wire analog sensor powered from 10
to 30V dc power DX80 device using the PWR
terminal.
Three-wire analog sensor using a
FlexPower™ Node and powered using the
Node’s switch power.