Banner SureCross DX80 Wireless Networks User Manual
Page 20

I/O 15 Control Messages
Control Code
in Hex (Dec)
Data Field in
Hex (Dec)
Control Code
and Data Field
in Decimal
Restrictions
Description
0x11 (17)
Bit Mask, see
description
4352
0 = all bits off
63 = all bits
on
Gateway Link failure. Set the outputs to default
states based on Bit Mask. Bit0 in the data field =
I/O 9, bit1 = I/O 10, etc. The Gateway Link Failure
flag must be set to enable this feature.
0x12 (18)
00
4608
Host Communication Timeout. Set all outputs on
this device to default states. The Host Link Failure
flag must be set to enable this feature.
0x13 (19)
Bit Mask
4864
Force device sample and report of selected enabled
inputs. The bit mask defines which I/O point will be
sampled. Bit 0 = I/O 1, Bit 1 = I/O 2, etc. A value of
0x3F (63) selects all inputs.
0x20 (32)
Node 0x00
through 0x38
(1–56)
8192+Node#
Gateway Only
Enable Site Survey between Gateway and Node
defined by the data field. All error messages from
the Gateway are ignored when running Site Survey.
Only one Node can participate in Site Survey at any
given time. To disable the Site Survey, use control
code 0x20 with Node 0. A Node must be enabled to
run the Site Survey, then disabled before selecting
the next Node.
0x30 (48)
0x00 through
0x18
12288-12312
FlexPower
™
Devices only
Enable all switched power outputs. The data field
selects the voltages.
0x00 = turn off
0x05 = 5V
0x07 = 7V
0x0F = 15V
0x14 = 20V
0x18 = 24V
0x31 (49)
12544-12586
Enable switched power #1, data field selects the
voltage (See above)
0x32 (50)
12800-12824
Enable switched power #2, data field selects the
voltage (See above)
0x33 (51)
13056-13080
Enable switched power #3, data field selects the
voltage (See above)
0x34 (52)
13312-13336
Enable switched power #4, data field selects the
voltage (See above)
Example: M-GAGE Baseline
To perform a baseline function on M-GAGE Node 1, write to register 31 (the Node’s register 15).
Reg 31
0x10 (16)
0x00
A baseline function on Node 1 will be initiated. (The command, both bytes together, in decimal would be 4096.)
Example: Forcing a Sample and Report
To force a sample and report of all Node 1’s inputs, write the command and data to register 31.
Host Controller Systems
20