Banner SureCross DX80 Wireless Networks User Manual
Page 18

Device Register 8 (Hex)
Message
Code
[15:8]
Data Field
[7:0]
Description
35
01
Radio Device (polling/heartbeat) Timeout. (Decimal value 13569.) A Node is
determined to be out of the wireless network based on the parameters defined for
polling or heartbeat. See the documentation in the UCT for polling or heartbeat
parameters and the timeout operation. When the least significant bit is on (1), an
error condition exists.
•
Run site survey to determine the quality of the RF link. If no communications
exist between the Gateway and Node, verify the power at the Node and all
antenna connections. The blocking of RF communications may also be a result
of environmental conditions that may have changed.
•
The battery of a battery powered Node may need to be replaced. Although
the LCD and device may appear functional, the battery may not have enough
capacity to handle the current requirements of RF communications.
36
01
Modbus time-out. A Gateway timeout (time of inactivity on the serial channel) was
detected. (Decimal value 13825.) When the least significant bit is on (1), an error
condition exists.
FE
--
Modbus register 8 device messages are disabled. The Modbus register 8 clears or
disables messages using the Gateway’s Modbus register 15. (Decimal values 65024
through 65279.)
Host Controller Systems
18