beautypg.com

Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual

Page 60

background image

Publication GMSI10-UM015B-EN-E - June 2011

60 Specifications

Relays

Number

Contacts

Failsafe

Latching

Voting Logic

Activation

Reset

Four relays, two sets of contacts each -
DPDT (2 Form C)

250V AC, 50/60 Hz, 3 A Resistive

Normally energized

The shutdown and alarm relays shall latch
when the conditions that activate them are
met.

Two-out-of-three
One-out-of-three

Low logic level (<0.8V) on the
overspeed/circuit fault inputs

Local reset switch on top of module
Remote reset switch wired to terminal base

Power

Module

Consumption

Heat Production

24V DC

120mA maximum

2.9 Watts (9.9 BTU/hr) maximum

Redundant Power: All XM Measurement and
Relay modules support redundant power. Each
module includes redundant power inputs on its
terminal base unit.

Environmental

Operating Temperature

Storage Temperature

Relative Humidity

-20 to +65°C (-4 to +149°F)

-30 to +85°C (-22 to +185°F)

95% non-condensing

All printed circuit boards are conformally coated
in accordance with IPC-A-610C.

Physical

Dimensions

Terminal Screw Torque

Height: 3.8in (97mm)
Width: 3.7in (94mm)
Depth: 3.7in (94mm)

7 pound-inches (0.6Nm)

XM-441 Technical Specifications

Product Feature

Specification