Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual
Page 60
Publication GMSI10-UM015B-EN-E - June 2011
60 Specifications
Relays
Number
Contacts
Failsafe
Latching
Voting Logic
Activation
Reset
Four relays, two sets of contacts each -
DPDT (2 Form C)
250V AC, 50/60 Hz, 3 A Resistive
Normally energized
The shutdown and alarm relays shall latch
when the conditions that activate them are
met.
Two-out-of-three
One-out-of-three
Low logic level (<0.8V) on the
overspeed/circuit fault inputs
Local reset switch on top of module
Remote reset switch wired to terminal base
Power
Module
Consumption
Heat Production
24V DC
120mA maximum
2.9 Watts (9.9 BTU/hr) maximum
Redundant Power: All XM Measurement and
Relay modules support redundant power. Each
module includes redundant power inputs on its
terminal base unit.
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
-20 to +65°C (-4 to +149°F)
-30 to +85°C (-22 to +185°F)
95% non-condensing
All printed circuit boards are conformally coated
in accordance with IPC-A-610C.
Physical
Dimensions
Terminal Screw Torque
Height: 3.8in (97mm)
Width: 3.7in (94mm)
Depth: 3.7in (94mm)
7 pound-inches (0.6Nm)
XM-441 Technical Specifications
Product Feature
Specification