Rockwell Automation 1606-XLP XM Electronic Overspeed Detection System User Manual
Page 43

Publication GMSI10-UM015B-EN-E - June 2011
Installing the XM Electronic Overspeed Detection System 43
Channel 1 and Channel 2 Indicator
Startup (Start) Indicator
Relay Indicators
Color
State
Description
No color
Off
• Normal operation within alarm limits on the XM-220
channel.
• No power applied to the module, look at XM-220
Module Status LED.
Yellow
Solid
An alert level alarm condition exists on the channel
(and no transducer fault, tachometer fault, or danger
level alarm condition exists).
Flashing
Tachometer fault (no transducer fault) condition exists
on the XM-220 channel.
Red
Solid
A danger level alarm condition exists on the XM-220
channel (and no transducer fault or tachometer fault
condition exists).
Flashing
A transducer fault condition exists on the XM-220
channel.
Color
State
Description
Yellow
Off
Startup period is not in effect.
Solid
Startup period is in effect.
• XM-220 module may be inhibiting the Tach Fault
alarm status.
• XM-220 module may be monitoring for locked rotor
conditions.
Color
State
Description
Red
Off
On-board relay is not activated.
Solid
On-board relay is activated.