205/1205 Interlock Register (Continued)
Bit: 7
Hex Value: 0080H
Sug. Var. Name:
WCI_MCR@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The M-Contactor Not Closed bit is set if the M-Contactor did not close at the expected
time.
Bit: 8
Hex Value:
01 OOH
Sug. Var. Name:
WFI_ILL@
Range:
N/A
Access:
Read
Only
UDC Error Code:
N/A
LED:
N/A
Description:
The More Than One Field Request bit is set when more than one incompatible Field
operating mode is requested at a time in register 100/1 100. The following operating modes are mutu-
ally exclusive:
l
Field Alpha Test
l
Field Identification Test
l
Field Run
This bit is also set if you have attempted to restart the drive without resetting the appropriate com-
mand bits from register 100/1 100. Recall that the bits in register 100/1 100 are edge-sensitive. See
Appendix G for additional information.
Bit: 9
Hex Value: 0200H
Sug. Var. Name:
WFI_CNF@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The Field Parameters Are Not Loaded bit is set if the field configuration parameters
have not been downloaded into the UDC module from the Programming Executive.
Bit:
10
Hex Value: 0400H
Sug. Var. Name:
WFI_GAN@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The Field Gains Not Loaded bit is set if field gains are zero, i.e., have not been auto-
tuned for or a UDC task containing the pre-defined gain variables has not been loaded.
Bit:
11
Hex Value: 0800H
Sug. Var. Name:
WFI_FLT@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The Field Faults Need to be Reset bit is set if previous field faults (register 202/1202),
i.e., field loss and line synchronization loss faults, have not been cleared.