4 meter port selection screen – Rockwell Automation SD3000 Drive Configuration, Programming User Manual
Page 18
l
Motor Base Speed (RPM)
Speed Safety Data Selections
Enter the motor’s base speed. This value is the motor’s top operating speed under full field and is
the speed when field weakening begins. This value is found on the motor’s nameplate and can
range from 0 to 3600 RPM.
l
Over Speed Trip (RPM)
Enter the overspeed trip point. This is the limit to be used for overspeed detection and can range
from 0 to 5000 RPM. When an analog tachometer is used, this value is used to scale the analog
voltage into RPM. A typical value is 110% of gear-in speed.
l
Tach Volts at Over Speed Trip
Enter the tachometer voltage that will be present when the motor is turning at the overspeed trip
point RPM. Enter the value as x.xx. The value can range from 5 to 9.75 volts.
l
None
Resolver Type Selections
Select this option if a resolver is not being used.
. X1, X2, X5
If a resolver is being used, select which type it is: either Xl, X2, or X5.
2.2.4 Meter Port Selection Screen
The Meter Port Selection parameter screen allows you to enter specific information about what
variables are to be output on the four PMI D/A channels (the four “meter” ports on the PMI Processor
module). See figure
2.7.
Meter Port
:
Armature
Current
Feedback (Counts)
,
Armature Current Reference
00)
5.00 Units/Volt
50.0 Units at 0 V
Meter
Armature
Current Feedback
0)
Value
l
o
Value
200.00 Units/Volt
2000.0
Units at 0 V
Figure 2.7 - Meter Port Selection Entry Screen
2-10