Rockwell Automation SD3000 Drive Configuration, Programming User Manual
Page 42
200/1 200
Drive Status Register (Continued)
Bit: 4
Hex Value:
001 OH
Sug. Var. Name:
FML_ON@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The Field Regulator On bit set whenever the field regulator loop is executing/enabled.
(See register 100/1 100, bit 4). When the request for the function is turned off, this bit will be turned
Off.
Bit: 5
Hex Value: 0020H
Sug. Var. Name:
FML_IDC@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The Field Identification Test Complete bit is set when the field identification test is fin-
ished.(See register 100/1 100, bit 5). When the request for the function is turned off, this bit will be
turned off.
Bit: 6
Hex Value: 0040H
Sug. Var. Name:
FML_LIMB
Range:
N/A Access: Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The Field Minor Loop in Limit bit is set when the advance of the firing angle is being
limited or the bridge is full on. This bit is normally off.
Bit: 8
Hex Value: 01
00H
Sug. Var. Name:
FLT@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The PMI Processor sets the Fault Detected bit when any fault is detected. (See Drive
Fault register 202/1 202). It is reset by bit 8 of register 100/1 100.
Bit: 9
Hex Value: 0200H
Sug. Var. Name:
WRN@
Range:
N/A
Access:
Read Only
UDC Error Code:
N/A
LED:
N/A
Description:
The PMI Processor sets the Warning Detected bit when any warning is detected. See
Drive Warning register 203/1 203. It is reset by bit 9 of register 100/1 100.
3-22