Demo Unit User Manual (AADvance Controller)

5-26

Document: 553850 Issue 1.2: March 2011

Configuring Digital Outputs

You can wire digital output channels to the following variable type and data structures:

BOOL (the gives the commanded state)

TK9_DO_Compact (provides three elements)

TK9_DO_Full (seven elements)

The structures provide additional information about the output, such as line fault

status and discrepancy status.

Note: The controller writes its digital outputs once per application cycle; the digital
output variables are also updated once per application cycle.

TK9_DO_COMPACT and TK9_DO_FULL (Digital Outputs)

The data structures for digital inputs (TK9_DO_COMPACT and TK9_DO_FULL)
provide the elements detailed in the tables.

Table 16:

TK9_DO_COMPACT Structure for Digital Outputs

Identifier Type

Description

Remarks

.DOP

BOOL

Input state

The commanded state to be passed to the
output channel

Set to TRUE to energize

Set to FALSE to de-energize

.LF

BOOL

Line fault

TRUE: no field supply is present, no load is

connected, or a short circuit is detected

.DIS BOOL

Discrepancy TRUE:

there is a discrepancy in current greater

than 1% between the channels of two modules in
a redundant configuration (†)

Table 17:

TK9_DO_FULL Structure for Digital Outputs

Identifier Type

Description

Remarks

.DOP

BOOL

Input state

The commanded state to be passed to the
output channel

Set to TRUE to energize

Set to FALSE to de-energize

.LF

BOOL

Line fault

TRUE: no field supply is present, no load is

connected, or a short circuit is detected