Processor Module B On-line
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is on-line
FALSE = The processor module is off-line
Default: TRUE
Description:
Reports that a processor module within a dual or triple modular redundant
configuration is present and is communicating through the inter-processor link to one
or both of its peers. Reports that a simplex processor module is present.
Processor Module C On-line
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is on-line
FALSE = The processor module is off-line
Default: TRUE
Description:
Reports that a processor module within a dual or triple modular redundant
configuration is present and is communicating through the inter-processor link to one
or both of its peers. Reports that a simplex processor module is present.
Processor Module A Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is healthy and its Healthy
LED indicator is green.
FALSE = The processor module is faulty and its Healthy LED indicator is red.
Description:
Reports the health status of a processor module.