Document: 553850 Issue 1.2: March 2011

4-5

Serial Port Protocols

The serial ports support the protocols listed in the table.

Table 5:

Serial Port Protocols

Type Description

RS485fd

Full-duplex, 4-wire connection with separate buses for

transmit and receive

RS485fdmux

Full-duplex, 4-wire connection with separate buses for

transmit and receive and tri-state outputs on the
transmit connections

RS485hdmux

Half duplex, 2-wire connection

Serial Port Parameters

Each serial port on the AADvance controller supports the set of control parameters as
detailed in the table.

Table 6:

Controller Serial Port Parameters

Description Value(s)

Default

Remarks

Baud

2,400, 4,800, 9,600,

19,200, 38,400,

57,600, 76,800 or
115,200

19,200

Data Bits

5 to 8

8

Parity

None, Odd or Even

None

Stop Bits

1 or 2

1

Type RS485fd

RS485fdmux

RS485hdmux

RS485hdmux

'fd' means 'full duplex'

'hd' means 'half duplex'

Note: Most systems use two bits after each data byte. The two bits are either a parity
bit (odd or even) and one stop bit, or no parity and two stop bits.