beautypg.com

Rockwell Automation AADvance Controller Demo Unit User Manual

Page 31

background image

Document: 553850 Issue 1.2: March 2011

3-3

Start All Programs AADvance AADvance Discover.

The AADvDiscover utility scans the network for controllers, and creates a
list.

4) Locate the controller in the list and make sure that the status of the controller is

Configurable.

5) Double-click on the MAC address in the Controller ID field.

The resource and IP Address dialog box opens.

6) Enter the resource value into the Resource Number field, click Apply.

Returning to the main window of the utility, the controller status will show
Pending Restart.

7) To complete the update, cycle the power to the controller.
8) Refresh the screen to confirm that the new resource number is displayed in the

resource field and the controller status is configurable.

The Resource Number must also be configured in the application, in the
Resource Properties.