Rockwell Automation AADvance Controller Demo Unit User Manual
Page 53

Document: 553850 Issue 1.2: March 2011
4-19
Processor Module B 24V1 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module C 24V1 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module A 24V2 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module B 24V2 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.