background image

Demo Unit User Manual (AADvance Controller)

4-18

Document: 553850 Issue 1.2: March 2011

Processor Module B Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = The 9110 processor module in the given slot is healthy and its Healthy
LED indicator is green.

FALSE = The processor module is faulty and its Healthy LED indicator is red.

Description:
Reports the health status of a processor module.

Processor Module C Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = The 9110 processor module in the given slot is healthy and its Healthy
LED indicator is green.

FALSE = The processor module is faulty and its Healthy LED indicator is red.

Description:

Reports the health status of a processor module.

Processor Module A 24V1 Power Feed Health

Direction: input to application from controller
Type: boolean
Values:

TRUE = power feed voltage is within specification (18 to 32V dc).

FALSE = power feed is outside specification.

Description:

Reports the health of power feed 1 (nominal 24V dc) to the 9110 processor module in
the given slot.