Installing the XM-360 Process Module 25
Connecting the Inputs
The XM-360 will accept signals from loop currents or voltage inputs. All six
input channels are electrically isolated from each other and from circuit power
and ground. The isolation provided is up to 250V.
Connecting a Voltage Input
Figures 2.13 to 2.18 show the wiring from a voltage input to the terminal base
unit of the XM-360 module.
Figure 2.13 0-5V Voltage Input to Channel 1 Wiring
IMPORTANT
With all the cable shields connected (six individual input
cables and six output cables), there are not enough chassis
terminals for each shield. Therefore, the cable shields
should be paired as depicted in the following illustrations.
Recommended practice is to use a crimp ferrule.
Alternatively, you can use a separate grounding block
mounted next to the module.
ATTENTION
You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. Recommended
practice is to ground the cable shield at the XM-360
terminal base and not at the field device. Any convenient
Chassis terminal may be used (see Terminal Block
Assignments on page 17).
TYPICAL WIRING FOR VOLTAGE INPUT
TO XM-360 PROCESS MODULE CHANNEL 1
41
19
20
Process
Output
Voltage
Com
V out
SHIELD
RED
BLK
RED
BLK