Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual
Page 63
![background image](/manuals/581043/63/background.png)
Troubleshooting
4-3
PowerFlex 700L Active Converter Power Module User Manual
PWM Sync Lost
46
➂
PWM Carrier synchronization was lost.
Verify wiring of carrier synchronization
cable.
Variations in the AC Line Faults
Ac Low Voltage
50
➂
AC line voltage was below the configured limit for the configured
time.
Verify proper input line voltage is present.
Ac High Voltage
51
➂
AC line voltage exceeded the configured limit for the configured
time.
Verify proper input line voltage is present.
Ac Low Frequency
52
➂
AC line frequency was below the configured limit for the
configured time.
Verify proper input line voltage is present.
Ac HighFrequency
53
➂
AC line frequency exceeded the configured limit for the configured
time.
Verify proper input line voltage is present.
Ac High dFdt
54
➂
Change in line frequency exceeded the configured limit.
Verify proper input line voltage is present.
Ac I Imbalance
55
➂
AC current balance exceeded the configured limit for the
configured time.
Verify proper input line voltage is present.
Ac V Imbalance
56
➂
AC voltage balance exceeded the configured limit for the
configured time.
Verify proper input line voltage is present.
DcLink Low Volt
57
DC link voltage was below the precharge open level.
Verify proper input line voltage is present.
Ride Thru Expire
58
Power dip ride through expired with precharge open.
Verify proper input line voltage is present.
Ride Thru Expire
59
Power dip ride through expired with precharge closed.
Verify proper input line voltage is present.
Overload Faults
IT Over Load
60
Operating current levels exceeded the rated overload.
Verify proper input line voltage is present.
Ambnt Over Temp
61
Measured ambient temperature exceeded the maximum limit.
Base Over Temp
62
IGBT base temperature exceeded the maximum limit.
Verify required drive cooling is present.
Junct Over Temp
63
IGBT junction temperature exceeded the maximum limit.
Verify required drive cooling is present.
Ntc Range Low
64
NTC temperature outside below rated temperature range.
Check for open or shorted NTC device.
Ntc Range High
65
NTC temperature outside above rated temperature range.
Check for open or shorted NTC device.
PS1 Fan Loss
66
Power Structure 1 detected a circulating fan was lost.
(2)
Verify internal circulating fans are turning.
PS1 Reactor Temp
67
Power Structure 1 detected the reactor thermal switch opened.
(2)
Verify reactor cooling fans are turning.
PS2 Fan Loss
68
Power Structure 2 detected a circulating fan was lost.
(3)
Verify internal circulating fans are turning.
PS2 Reactor Temp
69
Power Structure 2 detected the reactor thermal switch opened.
(3)
Verify reactor cooling fans are turning.
Input Filter Fault
FiltCap Contactr
70
The detected state (open/closed) of the input filter capacitor bank
contactor does not match the commanded state.
Verify wiring of filter capacitor contactor.
Stand Alone Unit (DPI MASTER) Faults
Port 1 Adapter
71
The communication card has detected a fault on the network.
(4)
Check DPI device event queue and
corresponding fault information for the
device.
Port 2 Adapter
72
The communication card has detected a fault on the network.
Port 3 Adapter
73
The communication card has detected a fault on the network.
Port 4 Adapter
74
The communication card has detected a fault on the network.
Port 5 Adapter
75
The communication card has detected a fault on the network.
Port 6 Adapter
76
The communication card has detected a fault on the network.
Port 1 DPI Loss
81
The DPI communication to a peripheral was lost.
1. If adapter was not intentionally
disconnected, check wiring to the port.
Replace wiring, port expander,
adapters, Main Control Board, or
complete Converter as required.
2. Check HIM connection.
3. If an adapter was intentionally
disconnected and the [Logic Mask] bit
for that adapter is set to “1,” this fault
will occur. To disable this fault, set the
[Logic Mask] bit for the adapter to “0.”
Port 2 DPI Loss
82
The DPI communication to a peripheral was lost.
Port 3 DPI Loss
83
The DPI communication to a peripheral was lost.
Port 4 DPI Loss
84
The DPI communication to a peripheral was lost.
Port 5 DPI Loss
85
The DPI communication to a peripheral was lost.
Port 6 DPI Loss
86
The DPI communication to a peripheral was lost.
(1)
See
for a description of fault types.
(2)
These faults only apply to Frame 3 power structures.
(3)
These faults are reserved for future use.
(4)
These faults only apply when operating the Active Converter as a Stand Alone unit (DPI Master).
Fault
No.
Type
(1)
Description
Action