Rockwell Automation 20L, LPM20 PowerFlex 700 Active Converter Power Module User Manual
Page 43
Programming and Parameters
3-7
PowerFlex 700L Active Converter Power Module User Manual
CO
MMA
N
D
Star
t /
Stop
053
[Turn Off Delay]
This parameter is used when parameter 50 - [Start Config] is set to “0” (Run On
Start) to select how long to keep the Converter enabled after the Inverter is
stopped.
Default:
Min/Max:
Units:
5.0 Sec
1.0/60.0 Sec
0.1 Sec
Setpoints
060
[DcLink Reference]
Sets the reference for the DC Link voltage when parameter 160 - [Voltage Loop
Sel] is set to “1” (Manual Ref).
Default:
Min/Max:
Units:
Rated*1.46 Vdc
300.0/1100.0 Vdc
0.1 Vdc
061
[kVAR Reference]
Sets the reference for the kVAR to produce. Positive values are a leading power
factor and negative values are a lagging power factor.
Default:
Min/Max:
Units:
0.0 KVAR
–3000.0/+3000.0 KVAR
0.1 KVAR
062
[Extern Cml Ref]
Sets the current reference as calculated by an external voltage loop. Values are
scaled so 4096 corresponds to Converter rated current.
Default:
Min/Max:
Units:
0
–8192/+8192
None
063
[Modulation Index]
Sets the modulation duty cycle when parameter 51 - [Option Select] Bit 4 Sim
ModIndex is enabled and the Converter is started.
Default:
Min/Max:
Units:
0.0%
0.0/100.0%
0.1%
064
[Modulation Freq]
Sets the simulated line frequency when parameter 51 - [Option Select] Bit 5 Sim
ModFreq is enabled and the Converter is started.
Default:
Min/Max:
Units:
0.0 Hz
0.0/60.0 Hz
0.1 Hz
Da
ta
E
xch
ang
e
070
[Converter Control]
A set of bits sent from the Inverter to control the Converter.
•
Bit 0 (Enable Cnvtr) – This bit is set by the Inverter when the drive is started. When parameter 50 - [Start Config] is set to “0” (Run
on Start), setting this bit closes the precharge bypass and enables the Converter voltage and current loops.
•
Bit 1 (700VC Invtr) – This bit is set when the Active Converter is communicating with an Inverter that has 700 Vector Control. It is
cleared when communicating with an Inverter that has 700S Phase II Control.
Fil
e
Gr
oup No.
Parameter Name & Description
Values
Bit
Definition
700VC In
vtr
En
ab
le Cn
vtr
Default
x
x
x
x
x
x
x
x
x
x
x
x
x
x
0
0
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = Disabled
1 = Enabled
x = Reserved