Programming and Parameters
3-11
PowerFlex 700L Active Converter Power Module User Manual
Dynamic Control File
Fil
e
Gr
oup No.
Parameter Name & Description
Values
D
Y
N
A
M
IC CO
N
T
R
O
L
Current
Loop
150
[Reduce Ilmt Sel]
Enables the use of a reduced current limit when in overload.
“Disabled” = The Converter current limit is always the value in parameter 100 -
[Active I Lmt].
“Enabled” = The Converter current limit will switch to the value set by parameter
101 - [Active OL I Lmt] when in overload.
Default:
Options:
1
0
1
“Disabled”
“Disabled”
“Enabled”
151
[Active I Cmd]
Displays the commanded active current.
Default:
Min/Max:
Units:
Read Only
-3276.7/+3276.7
0.1 Amps
152
[Inductance]
Sets the input filter inductance. When set to non-zero, this value is used to
calculate the tuning coefficients for the current loop CML Ki and Kp.
Default:
Min/Max:
Units:
Rated µH
0/32767 µH
1 µH
153
[CML Bandwidth]
Sets the Current Minor Loop bandwidth. When set to non-zero, this value is
used to calculate the tuning coefficients for the current loop CML Ki and Kp.
Default:
Min/Max:
Units:
1500 Rad/sec
0/4000 Rad/sec
1 Rad/sec
154
[CML Damping]
Sets the Current Minor Loop damping. When set to non-zero, this value is used
to calculate the tuning coefficients for the current loop CML Ki and Kp.
Default:
Min/Max:
Units:
1.6
0.5/5.0
None
155
[CML Ki]
Tunes the integral gain of the current loop.
Default:
Min/Max:
Units:
Drive Size Dependent
0/32767
None
156
[CML Kp]
Tunes the proportional gain of the current loop.
Default:
Min/Max:
Units:
Drive Size Dependent
0/32767
None
157
[PF Bandwidth]
Sets the bandwidth of the current regulator maintaining the desired power factor.
This is used only when parameter 051 - [Option Select] Bit 1 (Unbal V Comp) is
set to "1" to enable unbalanced voltage compensation.
Default:
Min/Max:
Units:
Drive Size Dependent
0/4000
None
158
[Reactive I Lmt]
Displays the calculated reactive current limit.
Default:
Min/Max:
Units:
Read Only
0.0/3000.0
0.1 Amps
159
[Reactive I Cmd]
Displays the commanded reactive current.
Default:
Min/Max:
Units:
Read Only
-3000.0/+3000.0
0.1 Amps
V
o
lta
g
e Loop
160
[Voltage Loop Sel]
Selects the operation of the voltage loop.
“Optimize Ref” = Vdc reference is calculated to minimize switching losses,
based on the measured AC Line voltage and the minimum voltage required by
the Inverter.
“Manual Ref” = The value set by parameter 060 - [DcLink Reference] is used for
Vdc reference.
“Regen Only” = Reserved for future.
“Open Loop” = The Converter outputs a sinusoidal voltage synchronized to the
AC line with an amplitude set by parameter 063 - [Modulation Index]. This
feature requires a password to operate.
Default:
Options:
0
0
1
2
3
“Optimize Ref”
“Optimize Ref”
“Manual Ref”
“Regen Only”
“Open Loop”
161
[DcLink Command]
Displays the commanded DC Link voltage.
Default:
Min/Max:
Units:
Read Only
0.0/1225.0
0.1 Vdc