Hardware – Rockwell Automation 9303 DRIVE TOOLS 32 VER 2.50 GETTING STARTED User Manual
Page 53
![background image](/manuals/580159/53/background.png)
Setting Up DH+ to RIO Block Transfer Pass Thru Communications
6-3
Using DH+ to RIO
Block Transfer
Pass Thru
Communications
With DH+ to RIO Block Transfer communications, you must use an internal
interface card (1784-KT, -KTX, -KTXD, or -PCMK) in your computer.
Important: If you are using an external converter, see “Using RS-232 to DH+
to RIO Block Transfer Pass Thru Communications” on page 6-7.
Hardware
Required Hardware
The hardware required for this type of communications depends on the drive
type. Refer to the following table:
Setting Up the Hardware
To use DriveTools32 with this type of communications, you must:
•
Ensure that the drive and adapter are properly installed and powered.
•
Ensure that cables are securely connected and protected from damage.
•
Ensure that block transfer is enabled in your adapter. If you are using a
1203-Gx1 or 1336-GM1 module, switch 1 on SW3 must be ON.
Important: Ensure that the ladder logic program and controller configuration
reflect the image table with Block Transfer enabled.
•
Note the Remote I/O adapter settings. You need to specify the rack and
group number when configuring a DriveTools32 application:
Drive
Required Drive Hardware
Required Computer Hardware
SCANport-Compatible
➀
Remote I/O Adapter (1203-GD1,
1203-GK1 or 1336-GM1) and
appropriate cable(s)
1784-KT, -KTX, -KTXD, or -PCMK
1336 FORCE
PLC Communications Adapter Board
(1336T-GT1EN)
1784-KT, -KTX, -KTXD, or -PCMK
1395
Node Adapter (1395-KP50) or
Multi-Communications Adapter
(1395-KP51)
1784-KT, -KTX, -KTXD, or -PCMK
➀
For a list of SCANport-compatible products, refer to Appendix A, Products Supported by DriveTools32.
Adapter
Refer To:
Remote I/O Adapter (1203-GD1, 1203-GK1 or
1336-GM1) and appropriate cable(s)
Bulletin 1203 Remote I/O Communications Module User
Manual
PLC Communications Adapter Board
(1336T-GT1EN)
1336 FORCE PLC Communications Adapter User Manual
Node Adapter (1395-KP50) or
Multi-Communications Adapter (1395-KP51)
Bulletin 1395 Multi-Communications Board Hardware/
Software Reference Manual